Five stages, a fixed fee agreed before mobilisation, and you know where you stand before we leave the building. We attend site anywhere in Ontario.
Twenty minutes with drawings or photographs. We confirm the triggers and quote a fixed fee.
Manuals, schematics and control architecture go through desk review before anyone travels.
Measurements, control verification and hands on testing with your operators present.
Findings referenced to the clause, ranked by risk, each with a specific corrective measure.
We re-verify the corrections and issue the compliance confirmation your file needs.
Most safeguarding failures we find are not missing barriers. They are interlocks wired through a standard control relay instead of a safety relay, safety functions bypassed in the PLC program, forced guided contacts that were never monitored, or a light curtain mounted inside its own calculated safety distance.
We verify the safety function end to end: sensor, logic and output. Required Performance Level is determined from severity, frequency of exposure and possibility of avoidance under ISO 13849-1, then the achieved Performance Level is assessed from category, MTTFd, diagnostic coverage and common cause failure. Minimum safety distance is calculated under ISO 13855 using measured overall system stopping performance, not the response time printed on the device.
Send drawings or photographs and we will tell you plainly whether a review is required, before any fee is discussed. We work across all of Ontario.
For anything specific to your equipment, call 613-983-2642.